Date Id Summary Products Score Patch Annotated
2020-12-11 CVE-2020-28214 A CWE-760: Use of a One-Way Hash with a Predictable Salt vulnerability exists in Modicon M221 (all references, all versions), that could allow an attacker to pre-compute the hash value using dictionary attack technique such as rainbow tables, effectively disabling the protection that an unpredictable salt would provide. Modicon_m221_firmware 5.5
2019-04-17 CVE-2019-10953 ABB, Phoenix Contact, Schneider Electric, Siemens, WAGO - Programmable Logic Controllers, multiple versions. Researchers have found some controllers are susceptible to a denial-of-service attack due to a flood of network packets. Pm554\-Tp\-Eth_firmware, Ilc_151_eth_firmware, Modicon_m221_firmware, 6ed1052\-1cc01\-0ba8_firmware, 6es7211\-1ae40\-0xb0_firmware, 6es7314\-6eh04\-0ab0_firmware, Bacnet\/ip_firmware, Ethernet_firmware, Knx_ip_firmware, Pfc100_firmware 7.5
2019-05-22 CVE-2018-7821 An Environment (CWE-2) vulnerability exists in SoMachine Basic, all versions, and Modicon M221(all references, all versions prior to firmware V1.10.0.0) which could cause cycle time impact when flooding the M221 ethernet interface while the Ethernet/IP adapter is activated. Modicon_m221_firmware, Somachine_basic 7.5
2019-05-22 CVE-2018-7822 An Incorrect Default Permissions (CWE-276) vulnerability exists in SoMachine Basic, all versions, and Modicon M221(all references, all versions prior to firmware V1.10.0.0) which could cause unauthorized access to SoMachine Basic resource files when logged on the system hosting SoMachine Basic. Modicon_m221_firmware, Somachine_basic 5.5
2019-05-22 CVE-2018-7823 A Environment (CWE-2) vulnerability exists in SoMachine Basic, all versions, and Modicon M221(all references, all versions prior to firmware V1.10.0.0) which could cause remote launch of SoMachine Basic when sending crafted ethernet message. Modicon_m221_firmware, Somachine_basic 5.3
2020-04-22 CVE-2020-7489 A CWE-74: Improper Neutralization of Special Elements in Output Used by a Downstream Component ('Injection') vulnerability exists on EcoStruxure Machine Expert – Basic or SoMachine Basic programming software (versions in security notification). The result of this vulnerability, DLL substitution, could allow the transference of malicious code to the controller. Ecostruxure_machine_expert, Modicon_m100_firmware, Modicon_m200_firmware, Modicon_m221_firmware, Somachine_basic 9.8