Product:

Modicon_m221_firmware

(Schneider\-Electric)
Repositories

Unknown:

This might be proprietary software.

#Vulnerabilities 16
Date Id Summary Products Score Patch Annotated
2020-04-22 CVE-2020-7489 A CWE-74: Improper Neutralization of Special Elements in Output Used by a Downstream Component ('Injection') vulnerability exists on EcoStruxure Machine Expert – Basic or SoMachine Basic programming software (versions in security notification). The result of this vulnerability, DLL substitution, could allow the transference of malicious code to the controller. Ecostruxure_machine_expert, Modicon_m100_firmware, Modicon_m200_firmware, Modicon_m221_firmware, Somachine_basic 9.8
2020-11-19 CVE-2020-7568 A CWE-200: Exposure of Sensitive Information to an Unauthorized Actor vulnerability exists in Modicon M221 (all references, all versions) that could allow non sensitive information disclosure when the attacker has captured the traffic between EcoStruxure Machine - Basic software and Modicon M221 controller. Modicon_m221_firmware 4.3
2020-11-19 CVE-2020-7565 A CWE-326: Inadequate Encryption Strength vulnerability exists in Modicon M221 (all references, all versions) that could allow the attacker to break the encryption key when the attacker has captured the traffic between EcoStruxure Machine - Basic software and Modicon M221 controller. Modicon_m221_firmware 7.3
2020-11-19 CVE-2020-7567 A CWE-311: Missing Encryption of Sensitive Data vulnerability exists in Modicon M221 (all references, all versions) that could allow the attacker to find the password hash when the attacker has captured the traffic between EcoStruxure Machine - Basic software and Modicon M221 controller and broke the encryption keys. Modicon_m221_firmware 5.7
2020-11-19 CVE-2020-7566 A CWE-334: Small Space of Random Values vulnerability exists in Modicon M221 (all references, all versions) that could allow the attacker to break the encryption keys when the attacker has captured the traffic between EcoStruxure Machine - Basic software and Modicon M221 controller. Modicon_m221_firmware 7.3
2020-12-11 CVE-2020-28214 A CWE-760: Use of a One-Way Hash with a Predictable Salt vulnerability exists in Modicon M221 (all references, all versions), that could allow an attacker to pre-compute the hash value using dictionary attack technique such as rainbow tables, effectively disabling the protection that an unpredictable salt would provide. Modicon_m221_firmware 5.5
2018-08-29 CVE-2018-7789 An Improper Check for Unusual or Exceptional Conditions vulnerability exists in Schneider Electric's Modicon M221 product (all references, all versions prior to firmware V1.6.2.0). The vulnerability allows unauthorized users to remotely reboot Modicon M221 using crafted programing protocol frames. Modicon_m221_firmware 7.5
2017-06-30 CVE-2017-6030 A Predictable Value Range from Previous Values issue was discovered in Schneider Electric Modicon PLCs Modicon M221, firmware versions prior to Version 1.5.0.0, Modicon M241, firmware versions prior to Version 4.0.5.11, and Modicon M251, firmware versions prior to Version 4.0.5.11. The affected products generate insufficiently random TCP initial sequence numbers that may allow an attacker to predict the numbers from previous values. This may allow an attacker to spoof or disrupt TCP connections. Modicon_m221_firmware, Modicon_m241_firmware, Modicon_m251_firmware 6.5
2018-08-29 CVE-2018-7790 An Information Management Error vulnerability exists in Schneider Electric's Modicon M221 product (all references, all versions prior to firmware V1.6.2.0). The vulnerability allows unauthorized users to replay authentication sequences. If an attacker exploits this vulnerability and connects to a Modicon M221, the attacker can upload the original program from the PLC. Modicon_m221_firmware 9.8
2018-08-29 CVE-2018-7791 A Permissions, Privileges, and Access Control vulnerability exists in Schneider Electric's Modicon M221 product (all references, all versions prior to firmware V1.6.2.0). The vulnerability allows unauthorized users to overwrite the original password with their password. If an attacker exploits this vulnerability and overwrite the password, the attacker can upload the original program from the PLC. Modicon_m221_firmware 9.8