Note:
This project will be discontinued after December 13, 2021. [more]
Product:
Bizviz
(Iconics)Repositories |
Unknown: This might be proprietary software. |
#Vulnerabilities | 7 |
Date | Id | Summary | Products | Score | Patch | Annotated |
---|---|---|---|---|---|---|
2020-07-16 | CVE-2020-12007 | A specially crafted communication packet sent to the affected devices could allow remote code execution and a denial-of-service condition due to a deserialization vulnerability. This issue affects: Mitsubishi Electric MC Works64 version 4.02C (10.95.208.31) and earlier, all versions; Mitsubishi Electric MC Works32 version 3.00A (9.50.255.02); ICONICS GenBroker64, Platform Services, Workbench, FrameWorX Server version 10.96 and prior; ICONICS GenBroker32 version 9.5 and prior. | Bizviz, Energy_analytix, Facility_analytix, Genesis32, Genesis64, Hyper_historian, Mobilehmi, Quality_analytix, Smart_energy_analytix, Mc_works, Mc_works32 | 9.8 | ||
2020-07-16 | CVE-2020-12013 | A specially crafted WCF client that interfaces to the may allow the execution of certain arbitrary SQL commands remotely. This affects: Mitsubishi Electric MC Works64 Version 4.02C (10.95.208.31) and earlier, all versions; Mitsubishi Electric MC Works32 Version 3.00A (9.50.255.02); ICONICS GenBroker64, Platform Services, Workbench, FrameWorX Server v10.96 and prior; ICONICS GenBroker32 v9.5 and prior. | Bizviz, Energy_analytix, Facility_analytix, Genesis32, Genesis64, Hyper_historian, Mobilehmi, Quality_analytix, Smart_energy_analytix, Mc_works32, Mc_works64 | 9.1 | ||
2020-07-16 | CVE-2020-12015 | A specially crafted communication packet sent to the affected systems could cause a denial-of-service condition due to improper deserialization. This issue affects: Mitsubishi Electric MC Works64 version 4.02C (10.95.208.31) and earlier, all versions; Mitsubishi Electric MC Works32 version 3.00A (9.50.255.02); ICONICS GenBroker64, Platform Services, Workbench, FrameWorX Server version 10.96 and prior; ICONICS GenBroker32 version 9.5 and prior. | Bizviz, Energy_analytix, Facility_analytix, Genesis32, Genesis64, Hyper_historian, Mobilehmi, Quality_analytix, Smart_energy_analytix, Mc_works, Mc_works32 | N/A | ||
2012-07-31 | CVE-2012-3018 | The lockout-recovery feature in the Security Configurator component in ICONICS GENESIS32 9.22 and earlier and BizViz 9.22 and earlier uses an improper encryption algorithm for generation of an authentication code, which allows local users to bypass intended access restrictions and obtain administrative access by predicting a challenge response. | Bizviz, Genesis32 | N/A | ||
2012-04-18 | CVE-2011-5089 | Buffer overflow in the Security Login ActiveX controls in ICONICS GENESIS32 8.05, 9.0, 9.1, and 9.2 and BizViz 8.05, 9.0, 9.1, and 9.2 allows remote attackers to cause a denial of service (application crash) or possibly execute arbitrary code via a long password. | Bizviz, Genesis32 | N/A | ||
2012-04-18 | CVE-2011-5088 | The GENESIS32 IcoSetServer ActiveX control in ICONICS GENESIS32 9.21 and BizViz 9.21 configures the trusted zone on the basis of user input, which allows remote attackers to execute arbitrary code via a crafted web site, related to a "Workbench32/WebHMI component SetTrustedZone Policy vulnerability." | Bizviz, Genesis32 | N/A | ||
2011-05-13 | CVE-2011-2089 | Stack-based buffer overflow in the SetActiveXGUID method in the VersionInfo ActiveX control in GenVersion.dll 8.0.138.0 in the WebHMI subsystem in ICONICS BizViz 9.x before 9.22 and GENESIS32 9.x before 9.22 allows remote attackers to execute arbitrary code via a long string in the argument. NOTE: some of these details are obtained from third party information. | Bizviz, Genesis32 | N/A |