Product:

Gateway

(Codesys)
Repositories

Unknown:

This might be proprietary software.

#Vulnerabilities 18
Date Id Summary Products Score Patch Annotated
2022-06-24 CVE-2022-31805 In the CODESYS Development System multiple components in multiple versions transmit the passwords for the communication between clients and servers unprotected. Development_system, Edge_gateway, Gateway, Hmi_sl, Opc_server, Plchandler, Plcwinnt, Runtime_toolkit, Sp_realtime_nt, Web_server 7.5
2019-08-15 CVE-2019-9012 An issue was discovered in 3S-Smart CODESYS V3 products. A crafted communication request may cause uncontrolled memory allocations in the affected CODESYS products and may result in a denial-of-service condition. All variants of the following CODESYS V3 products in all versions prior to v3.5.14.20 that contain the CmpGateway component are affected, regardless of the CPU type or operating system: CODESYS Control for BeagleBone, CODESYS Control for emPC-A/iMX6, CODESYS Control for IOT2000,... Control_for_beaglebone_sl, Control_for_empc\-A\/imx6_sl, Control_for_iot2000_sl, Control_for_linux_sl, Control_for_pfc100_sl, Control_for_pfc200_sl, Control_for_raspberry_pi_sl, Control_runtime_toolkit, Development_system, Gateway 7.5
2019-02-19 CVE-2018-20026 Improper Communication Address Filtering exists in CODESYS V3 products versions prior V3.5.14.0. Control_for_beaglebone_sl, Control_for_empc\-A\/imx6_sl, Control_for_iot2000_sl, Control_for_linux_sl, Control_for_pfc100_sl, Control_for_pfc200_sl, Control_for_raspberry_pi_sl, Control_rte_sl, Control_rte_sl_\(For_beckhoff_cx\), Control_runtime_toolkit, Control_win_sl, Development_system_v3, Gateway, Hmi_sl, Opc_server, Plchandler, Safety_sil2, Targetvisu_sl 7.5
2019-08-15 CVE-2019-9010 An issue was discovered in 3S-Smart CODESYS V3 products. The CODESYS Gateway does not correctly verify the ownership of a communication channel. All variants of the following CODESYS V3 products in all versions prior to v3.5.14.20 that contain the CmpGateway component are affected, regardless of the CPU type or operating system: CODESYS Control for BeagleBone, CODESYS Control for emPC-A/iMX6, CODESYS Control for IOT2000, CODESYS Control for Linux, CODESYS Control for PFC100, CODESYS Control... Control_for_beaglebone_sl, Control_for_empc\-A\/imx6_sl, Control_for_iot2000_sl, Control_for_linux_sl, Control_for_pfc100_sl, Control_for_pfc200_sl, Control_for_raspberry_pi_sl, Control_runtime_toolkit, Development_system, Gateway 9.8
2022-07-11 CVE-2022-30791 In CmpBlkDrvTcp of CODESYS V3 in multiple versions an uncontrolled ressource consumption allows an unauthorized attacker to block new TCP connections. Existing connections are not affected. Control_for_beaglebone, Control_for_empc\-A\/imx6, Control_for_iot2000_sl, Control_for_linux_sl, Control_for_pfc100_sl, Control_for_pfc200_sl, Control_for_plcnext, Control_for_raspberry_pi_sl, Control_for_wago_touch_panels_600, Control_rte_sl, Control_rte_sl_\(For_beckhoff_cx\), Control_runtime_system_toolkit, Control_win, Development_system, Edge_gateway, Embedded_target_visu_toolkit, Gateway, Hmi, Remote_target_visu_toolkit 7.5
2022-07-11 CVE-2022-30792 In CmpChannelServer of CODESYS V3 in multiple versions an uncontrolled ressource consumption allows an unauthorized attacker to block new communication channel connections. Existing connections are not affected. Control_for_beaglebone, Control_for_empc\-A\/imx6, Control_for_iot2000_sl, Control_for_linux_sl, Control_for_pfc100_sl, Control_for_pfc200_sl, Control_for_plcnext, Control_for_raspberry_pi_sl, Control_for_wago_touch_panels_600, Control_rte_sl, Control_rte_sl_\(For_beckhoff_cx\), Control_runtime_system_toolkit, Control_win, Development_system, Edge_gateway, Embedded_target_visu_toolkit, Gateway, Hmi, Remote_target_visu_toolkit 7.5
2022-06-24 CVE-2022-31802 In CODESYS Gateway Server V2 for versions prior to V2.3.9.38 only a part of the the specified password is been compared to the real CODESYS Gateway password. An attacker may perform authentication by specifying a small password that matches the corresponding part of the longer real CODESYS Gateway password. Gateway 9.8
2022-06-24 CVE-2022-31803 In CODESYS Gateway Server V2 an insufficient check for the activity of TCP client connections allows an unauthenticated attacker to consume all available TCP connections and prevent legitimate users or clients from establishing a new connection to the CODESYS Gateway Server V2. Existing connections are not affected and therefore remain intact. Gateway 5.3
2022-06-24 CVE-2022-31804 The CODESYS Gateway Server V2 does not verifiy that the size of a request is within expected limits. An unauthenticated attacker may allocate an arbitrary amount of memory, which may lead to a crash of the Gateway due to an out-of-memory condition. Gateway 7.5
2022-04-07 CVE-2022-22513 An authenticated remote attacker can cause a null pointer dereference in the CmpSettings component of the affected CODESYS products which leads to a crash. Control_for_beaglebone_sl, Control_for_beckhoff_cx9020, Control_for_empc\-A\/imx6_sl, Control_for_iot2000_sl, Control_for_linux_sl, Control_for_pfc100_sl, Control_for_pfc200_sl, Control_for_plcnext_sl, Control_for_raspberry_pi_sl, Control_for_wago_touch_panels_600_sl, Control_rte_sl, Control_rte_sl_\(For_beckhoff_cx\), Control_runtime_system_toolkit, Control_win_sl, Development_system, Edge_gateway, Embedded_target_visu_toolkit, Gateway, Hmi_sl, Remote_target_visu_toolkit 6.5