#Vulnerabilities 40
Date Id Summary Products Score Patch Annotated
2020-03-11 CVE-2019-5155 An exploitable command injection vulnerability exists in the cloud connectivity feature of WAGO PFC200. An attacker can inject operating system commands into any of the parameter values contained in the firmware update command. This affects WAGO PFC200 Firmware version 03.02.02(14), version 03.01.07(13), and version 03.00.39(12) Pfc200_firmware N/A
2020-03-11 CVE-2019-5134 An exploitable regular expression without anchors vulnerability exists in the Web-Based Management (WBM) authentication functionality of WAGO PFC200 versions 03.00.39(12) and 03.01.07(13), and WAGO PFC100 version 03.00.39(12). A specially crafted authentication request can bypass regular expression filters, resulting in sensitive information disclosure. Pfc100_firmware, Pfc200_firmware N/A
2020-03-11 CVE-2019-5168 An exploitable command injection vulnerability exists in the iocheckd service ‘I/O-Check’ function of the WAGO PFC 200 version 03.02.02(14). An attacker can send a specially crafted XML cache file At 0x1e8a8 the extracted domainname value from the xml file is used as an argument to /etc/config-tools/edit_dns_server domain-name=<contents of domainname node> using sprintf().This command is later executed via a call to system(). Pfc200_firmware N/A
2020-03-11 CVE-2019-5167 An exploitable command injection vulnerability exists in the iocheckd service ‘I/O-Check’ function of the WAGO PFC 200 version 03.02.02(14). At 0x1e3f0 the extracted dns value from the xml file is used as an argument to /etc/config-tools/edit_dns_server %s dns-server-nr=%d dns-server-name=<contents of dns node> using sprintf(). This command is later executed via a call to system(). This is done in a loop and there is no limit to how many dns entries will be parsed from the xml file. Pfc200_firmware N/A
2020-03-11 CVE-2019-5161 An exploitable remote code execution vulnerability exists in the Cloud Connectivity functionality of WAGO PFC200 versions 03.02.02(14), 03.01.07(13), and 03.00.39(12). A specially crafted XML file will direct the Cloud Connectivity service to download and execute a shell script with root privileges. Pfc200_firmware N/A
2020-03-11 CVE-2019-5149 The WBM web application on firmwares prior to 03.02.02 and 03.01.07 on the WAGO PFC100 and PFC2000, respectively, runs on a lighttpd web server and makes use of the FastCGI module, which is intended to provide high performance for all Internet applications without the penalties of Web server APIs. However, the default configuration of this module appears to limit the number of concurrent php-cgi processes to two, which can be abused to cause a denial of service of the entire web server. This... Pfc100_firmware, Pfc200_firmware N/A
2020-03-12 CVE-2019-5177 An exploitable stack buffer overflow vulnerability vulnerability exists in the iocheckd service ‘I/O-Check’ functionality of WAGO PFC 200 Firmware version 03.02.02(14). The destination buffer sp+0x440 is overflowed with the call to sprintf() for any domainname values that are greater than 1024-len(‘/etc/config-tools/edit_dns_server domain-name=‘) in length. A domainname value of length 0x3fa will cause the service to crash. Pfc200_firmware N/A
2020-01-08 CVE-2019-5082 An exploitable heap buffer overflow vulnerability exists in the iocheckd service I/O-Check functionality of WAGO PFC200 Firmware version 03.01.07(13), WAGO PFC200 Firmware version 03.00.39(12), and WAGO PFC100 Firmware version 03.00.39(12). A specially crafted set of packets can cause a heap buffer overflow, potentially resulting in code execution. An attacker can send unauthenticated packets to trigger this vulnerability. Pfc100_firmware, Pfc200_firmware N/A
2018-02-13 CVE-2018-5459 An Improper Authentication issue was discovered in WAGO PFC200 Series 3S CoDeSys Runtime versions 2.3.X and 2.4.X. An attacker can execute different unauthenticated remote operations because of the CoDeSys Runtime application, which is available via network by default on Port 2455. An attacker could execute some unauthenticated commands such as reading, writing, or deleting arbitrary files, or manipulate the PLC application during runtime by sending specially-crafted TCP packets to Port 2455. Pfc200_firmware 9.8
2017-02-13 CVE-2016-9362 An issue was discovered in WAGO 750-8202/PFC200 prior to FW04 (released August 2015), WAGO 750-881 prior to FW09 (released August 2016), and WAGO 0758-0874-0000-0111. By accessing a specific uniform resource locator (URL) on the web server, a malicious user is able to edit and to view settings without authenticating. 750\-Xxxx_series_firmware, 758\-Xxxx_series_firmware, Pfc200_firmware 9.1