Note:
This project will be discontinued after December 13, 2021. [more]
Product:
Micrologix_1100_firmware
(Rockwellautomation)Repositories |
Unknown: This might be proprietary software. |
#Vulnerabilities | 14 |
Date | Id | Summary | Products | Score | Patch | Annotated |
---|---|---|---|---|---|---|
2020-03-16 | CVE-2020-6980 | Rockwell Automation MicroLogix 1400 Controllers Series B v21.001 and prior, Series A, all versions, MicroLogix 1100 Controller, all versions, RSLogix 500 Software v12.001 and prior, If Simple Mail Transfer Protocol (SMTP) account data is saved in RSLogix 500, a local attacker with access to a victim’s project may be able to gather SMTP server authentication data as it is written to the project file in cleartext. | Micrologix_1100_firmware, Micrologix_1400_a_firmware, Micrologix_1400_b_firmware, Rslogix_500 | 3.3 | ||
2020-03-16 | CVE-2020-6984 | Rockwell Automation MicroLogix 1400 Controllers Series B v21.001 and prior, Series A, all versions, MicroLogix 1100 Controller, all versions, RSLogix 500 Software v12.001 and prior, The cryptographic function utilized to protect the password in MicroLogix is discoverable. | Micrologix_1100_firmware, Micrologix_1400_a_firmware, Micrologix_1400_b_firmware, Rslogix_500 | 7.5 | ||
2020-03-16 | CVE-2020-6988 | Rockwell Automation MicroLogix 1400 Controllers Series B v21.001 and prior, Series A, all versions, MicroLogix 1100 Controller, all versions, RSLogix 500 Software v12.001 and prior, A remote, unauthenticated attacker can send a request from the RSLogix 500 software to the victim’s MicroLogix controller. The controller will then respond to the client with used password values to authenticate the user on the client-side. This method of authentication may allow an attacker to bypass... | Micrologix_1100_firmware, Micrologix_1400_a_firmware, Micrologix_1400_b_firmware, Rslogix_500 | 7.5 | ||
2020-03-16 | CVE-2020-6990 | Rockwell Automation MicroLogix 1400 Controllers Series B v21.001 and prior, Series A, all versions, MicroLogix 1100 Controller, all versions, RSLogix 500 Software v12.001 and prior, The cryptographic key utilized to help protect the account password is hard coded into the RSLogix 500 binary file. An attacker could identify cryptographic keys and use it for further cryptographic attacks that could ultimately lead to a remote attacker gaining unauthorized access to the controller. | Micrologix_1100_firmware, Micrologix_1400_a_firmware, Micrologix_1400_b_firmware, Rslogix_500 | 9.8 | ||
2021-07-09 | CVE-2021-33012 | Rockwell Automation MicroLogix 1100, all versions, allows a remote, unauthenticated attacker sending specially crafted commands to cause the PLC to fault when the controller is switched to RUN mode, which results in a denial-of-service condition. If successfully exploited, this vulnerability will cause the controller to fault whenever the controller is switched to RUN mode. | Micrologix_1100_firmware | 8.6 | ||
2022-07-20 | CVE-2022-2179 | The X-Frame-Options header in Rockwell Automation MicroLogix 1100/1400 Versions 21.007 and prior is not configured in the HTTP response, which could allow clickjacking attacks. | Micrologix_1100_firmware, Micrologix_1400_firmware | 6.5 | ||
2022-12-16 | CVE-2022-3166 | Rockwell Automation was made aware that the webservers of the Micrologix 1100 and 1400 controllers contain a vulnerability that may lead to a denial-of-service condition. The security vulnerability could be exploited by an attacker with network access to the affected systems by sending TCP packets to webserver and closing it abruptly which would cause a denial-of-service condition for the web server application on the device | Micrologix_1100_firmware, Micrologix_1400_firmware | 7.5 | ||
2022-12-16 | CVE-2022-46670 | Rockwell Automation was made aware of a vulnerability by a security researcher from Georgia Institute of Technology that the MicroLogix 1100 and 1400 controllers contain a vulnerability that may give an attacker the ability to accomplish remote code execution. The vulnerability is an unauthenticated stored cross-site scripting vulnerability in the embedded webserver. The payload is transferred to the controller over SNMP and is rendered on the homepage of the embedded website. | Micrologix_1100_firmware, Micrologix_1400\-A_firmware, Micrologix_1400\-B_firmware, Micrologix_1400\-C_firmware, Micrologix_1400_firmware | 6.1 | ||
2019-04-25 | CVE-2019-10955 | In Rockwell Automation MicroLogix 1400 Controllers Series A, All Versions Series B, v15.002 and earlier, MicroLogix 1100 Controllers v14.00 and earlier, CompactLogix 5370 L1 controllers v30.014 and earlier, CompactLogix 5370 L2 controllers v30.014 and earlier, CompactLogix 5370 L3 controllers (includes CompactLogix GuardLogix controllers) v30.014 and earlier, an open redirect vulnerability could allow a remote unauthenticated attacker to input a malicious link to redirect users to a... | Compactlogix_5370_l1_firmware, Compactlogix_5370_l2_firmware, Compactlogix_5370_l3_firmware, Micrologix_1100_firmware, Micrologix_1400_a_firmware, Micrologix_1400_b_firmware | 6.1 | ||
2015-10-28 | CVE-2015-6492 | Allen-Bradley MicroLogix 1100 devices before B FRN 15.000 and 1400 devices before B FRN 15.003 allow remote attackers to cause a denial of service (memory corruption and device crash) via a crafted HTTP request. | Micrologix_1100_firmware, Micrologix_1400_firmware | N/A |