Product:

Factorytalk_services_platform

(Rockwellautomation)
Repositories

Unknown:

This might be proprietary software.

#Vulnerabilities 12
Date Id Summary Products Score Patch Annotated
2021-03-03 CVE-2021-22681 Rockwell Automation Studio 5000 Logix Designer Versions 21 and later, and RSLogix 5000 Versions 16 through 20 use a key to verify Logix controllers are communicating with Rockwell Automation CompactLogix 1768, 1769, 5370, 5380, 5480: ControlLogix 5550, 5560, 5570, 5580; DriveLogix 5560, 5730, 1794-L34; Compact GuardLogix 5370, 5380; GuardLogix 5570, 5580; SoftLogix 5800. Rockwell Automation Studio 5000 Logix Designer Versions 21 and later and RSLogix 5000: Versions 16 through 20 are... Factorytalk_services_platform, Rslogix_5000, Studio_5000_logix_designer 9.8
2022-04-01 CVE-2021-32960 Rockwell Automation FactoryTalk Services Platform v6.11 and earlier, if FactoryTalk Security is enabled and deployed contains a vulnerability that may allow a remote, authenticated attacker to bypass FactoryTalk Security policies based on the computer name. If successfully exploited, this may allow an attacker to have the same privileges as if they were logged on to the client machine. Factorytalk_services_platform 8.8
2022-02-24 CVE-2020-14478 A local, authenticated attacker could use an XML External Entity (XXE) attack to exploit weakly configured XML files to access local or remote content. A successful exploit could potentially cause a denial-of-service condition and allow the attacker to arbitrarily read any local file via system-level services. Factorytalk_services_platform 7.1
2021-03-18 CVE-2020-14516 In Rockwell Automation FactoryTalk Services Platform Versions 6.10.00 and 6.11.00, there is an issue with the implementation of the SHA-256 hashing algorithm with FactoryTalk Services Platform that prevents the user password from being hashed properly. Factorytalk_services_platform 10.0
2020-06-23 CVE-2020-12033 In Rockwell Automation FactoryTalk Services Platform, all versions, the redundancy host service (RdcyHost.exe) does not validate supplied identifiers, which could allow an unauthenticated, adjacent attacker to execute remote COM objects with elevated privileges. Factorytalk_services_platform N/A
2020-03-23 CVE-2020-6967 In Rockwell Automation all versions of FactoryTalk Diagnostics software, a subsystem of the FactoryTalk Services Platform, FactoryTalk Diagnostics exposes a .NET Remoting endpoint via RNADiagnosticsSrv.exe at TCPtcp/8082, which can insecurely deserialize untrusted data. Factorytalk_services_platform N/A
2019-01-24 CVE-2018-18981 In Rockwell Automation FactoryTalk Services Platform 2.90 and earlier, a remote unauthenticated attacker could send numerous crafted packets to service ports resulting in memory consumption that could lead to a partial or complete denial-of-service condition to the affected services. Factorytalk_services_platform 7.5
2015-03-30 CVE-2014-9209 Untrusted search path vulnerability in the Clean Utility application in Rockwell Automation FactoryTalk Services Platform before 2.71.00 and FactoryTalk View Studio 8.00.00 and earlier allows local users to gain privileges via a Trojan horse DLL in an unspecified directory. Factorytalk_services_platform, Factorytalk_view_studio N/A
2013-04-18 CVE-2012-4714 Integer overflow in RNADiagnostics.dll in Rockwell Automation FactoryTalk Services Platform (FTSP) CPR9, CPR9-SR1, CPR9-SR2, CPR9-SR3, CPR9-SR4, CPR9-SR5, CPR9-SR5.1, and CPR9-SR6 allows remote attackers to cause a denial of service (service outage or RNADiagReceiver.exe daemon crash) via UDP data that specifies a large integer value. Factorytalk_services_platform N/A
2013-04-18 CVE-2012-4713 Integer signedness error in RNADiagnostics.dll in Rockwell Automation FactoryTalk Services Platform (FTSP) CPR9, CPR9-SR1, CPR9-SR2, CPR9-SR3, CPR9-SR4, CPR9-SR5, CPR9-SR5.1, and CPR9-SR6 allows remote attackers to cause a denial of service (service outage or RNADiagReceiver.exe daemon crash) via UDP data that specifies a negative integer value. Factorytalk_services_platform N/A